Analysis of Energy Conservation Options for USDOE Child Development Center, Final Summary Report
Visit the Energy Systems Laboratory Homepage.
| Title: | Analysis of Energy Conservation Options for USDOE Child Development Center, Final Summary Report |
| Author: | Bou-Saada, T. E.; Haberl, J. S. |
| Abstract: | The U.S.D.O.E. Forrestal Child Development Center (CDC) was designed to be a "showpiece" model building. Its construction included energy efficient features such as efficient lighting, a photovoltaic system, an energy management system, lighting controls, envelope improvements, clerestory windows, energy efficient heat pumps, and a solar hot water system. The architect's estimate of the energy savings from these measures totaled 31.6 million Watt-hours per year (MWh/yr), an annual savings of about $1,580 (at $0.05/kWh). This study calculated a total annual energy savings of 23.2 MWh per year for the CDC; a savings of $1,160. |
| Description: | This report presents the results of a study that verifies the energy savings due to the individual ECOs through the use of a calibrated DOE-2 simulation. The results show that roughly 73% of the savings estimated by the GSA architect can be accounted for by the calibrated simulation. This compares very well when one considers that the large differences were contributed by the envelope improvements and the clerestory windows. If these two ECOs were omitted, 90% of the savings can be accounted for by the calibrated simulation. |
| Publisher: | Energy Systems Laboratory (http://esl.tamu.edu), Texas A&M University |
| Subject: | USDOE Forrestal Child Development Center energy efficiency photovoltaic DOE-2 simulation |
| URI: | http://handle.tamu.edu/1969.1/2147 |
| Date: | 1994 |
Files in this item
| Files | Size | Format | View |
|---|---|---|---|
| ESL-TR-94-12-11.pdf | 14.02Mb | application/pdf |
View/ |
This item appears in the following Collection(s)
-
Technical Reports
Technical Reports from the Energy Systems Laboratory
Browse