Investigation of a radiantly heated and cooled office with an integrated desiccant ventilation unit

Show simple item record

dc.contributor.advisor Claridge, David E. en_US
dc.creator Gong, Xiangyang en_US
dc.date.accessioned 2010-01-14T23:59:32Z en_US
dc.date.accessioned 2010-01-16T01:55:15Z
dc.date.available 2010-01-14T23:59:32Z en_US
dc.date.available 2010-01-16T01:55:15Z
dc.date.created 2007-08 en_US
dc.date.issued 2009-05-15 en_US
dc.identifier.uri http://hdl.handle.net/1969.1/ETD-TAMU-1559
dc.description.abstract Radiant heating and cooling has a reputation of increasing the comfort level and reducing the energy consumption of buildings. The main advantages of radiant heating and cooling are low operational noise and reduced fan power cost. Radiant heating and cooling has been supplied in several forms, including floor heating, ceiling heating and cooling, radiant panels and façade heating and cooling. Among them, façade heating and cooling is the most recently developed system. This dissertation provides a comprehensive study of several technical issues relative to radiant heating and cooling systems that have received little attention in previous research. The following aspects are covered in this dissertation: First, a heat transfer model of mullion radiators, one type of façade heating and cooling, is developed and verified by measured performance data. The simulation demonstrates that the heating or cooling capacity of mullion radiators is a semi-linear function of supply water temperature and is affected by the thermal conductive resistance of mullion tubes, the room air temperature, the supply water flow rate, and the outside air temperature. Second, the impact of the positions of radiators on energy consumption and thermal comfort is studied. This dissertation compares the heating load and comfort level as measured by uniformity of operative temperature for two different layouts of radiators in the same geometric space. The air exchange rate has been identified as an important factor which affects energy saving benefits of the radiant heating systems. Third, the infiltration and the interaction of infiltration and mechanical ventilation air to produce moisture condensation in a radiantly cooled office are examined. The infiltration of the studied office is also explored by on-site blower door measurement, by analyzing measured CO2 concentration data, and through modeling. This investigation shows the infiltration level of the studied office to range between 0.46 and 1.03 air changes per hour (ACH). Fourth, the integrated sensible heating and cooling system is simulated and compared with a single duct variable air volume (VAV) system. The results show that, at the current infiltration level, the studied sensible heating and cooling system with an integrated active desiccant ventilation unit consumes 5.6% more primary energy than a single duct VAV system; it would consumes 11.4% less primary energy when the system is integrated with a presumed passive desiccant ventilation unit. en_US
dc.format.medium electronic en_US
dc.format.mimetype application/pdf en_US
dc.language.iso en_US en_US
dc.subject Radiant heating en_US
dc.subject Radiant Cooling en_US
dc.subject Desiccant Ventilation Unit en_US
dc.subject Mullion Radiator en_US
dc.subject Radiant Panels en_US
dc.subject Passive Desiccant Unit en_US
dc.subject Active Desiccant Unit en_US
dc.title Investigation of a radiantly heated and cooled office with an integrated desiccant ventilation unit en_US
dc.type Book en
dc.type Thesis en
thesis.degree.department Mechanical Engineering en_US
thesis.degree.discipline Mechanical Engineering en_US
thesis.degree.grantor Texas A&M University en_US
thesis.degree.name Doctor of Philosophy en_US
thesis.degree.level Doctoral en_US
dc.contributor.committeeMember Archer, David H. en_US
dc.contributor.committeeMember Culp, Charles en_US
dc.contributor.committeeMember Heffington, Warren en_US
dc.contributor.committeeMember Turner, W. Dan en_US
dc.type.genre Electronic Dissertation en_US
dc.type.material text en_US
dc.format.digitalOrigin born digital en_US


Files in this item

Files Size Format View
GONG-DISSERTATION.pdf 6.223Mb PDF View/Open

This item appears in the following Collection(s)

Show simple item record